CVE-2026-3611
Description
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Predictions
Heuristic predictions, AS-IS, for prioritization only.
Mitigations
No mitigations published for this CVE yet.
The vendor-content worker queues fetches as references arrive (check back in a few minutes). Or โ if you've already worked around this in production โ publish your fix to the community-verified tier.
โ Propose a mitigation on Community โ Mitigations published via the community go through AI scoring + 2 human reviewers + 7-day silent objection window before landing here withsource_tier=community-verified.
References
CWEs
CWE-306
Community-verified mitigations for this CVE will appear above when contributors publish them.